Abstract

The equivalence conditions between homogeneous and two-layer earth structures are investigated in this paper. The analysis is based on the comparison between the two-layer and the homogeneous earth return impedance relations. The aim is the derivation of a new simple formula to connect the homogeneous earth equivalent resistivity with the two-layer earth electromagnetic and geometric properties. Thus, the relatively simple expressions for the impedance calculation of the homogeneous earth case can be used for two-layer earth models. The new formula is implemented for six actual cases of two-layer earth models. The two-layer earth impedances are calculated for various configurations, including overhead transmission lines, underground cable systems and a combination of overhead line and underground conductor. The calculated impedances are compared to the corresponding for the homogeneous earth, using the equivalent resistivity given by the new formula.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call