Abstract

This paper presents an equivalent time-domain grid-following inverter-based generator model, which can be used in Electromagnetic Transients Programs (EMTP). It is developed in the Alternative Transients Program (ATP) using the ATPDraw graphical interface. A complete benchmark photovoltaic model available in ATP/ATPDraw environment is taken as reference to evaluate the proposed model under steady-state and fault scenarios. The obtained results showed that the proposed model is simpler and less time-consuming than the complete model, being capable of easily consider the implementation of different components/controls of Inverter-Based Resources (IBR) in EMTP. The settings used in the implemented control schemes proved to be effective, resulting in an average error of about 2.33% during fault conditions. Also, a reduction of about 70 % in the execution time was achieved when compared to the analyzed benchmark one, attesting its usefulness for power system studies with high presence of grid-following IBRs.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call