Abstract

Electrical equipment grounding and bonding conductors must be sized to withstand the maximum fault currents imposed during abnormal system conditions. It is noted that many low-voltage distribution systems do not contain adequately sized equipment grounding conductors and bonding jumpers, compromising personnel and system safety. It is emphasized that proper consideration of conductor withstand ratings provides improved equipment grounding, system reliability, and safety. Examples are presented which illustrate the engineering and design issues associated with proper selection and sizing of the equipment grounding conductor and associated bonding conductors. Particular consideration is given to insulated conductor withstand ratings, bare conductor withstand ratings, and conductor sizing using a current-limiting device. It is concluded that it is the responsibility of the design engineer to comply with the National Electrical Code requirements as well as to understand the nuances of proper electrical protection associated with component and equipment withstandability. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.