Abstract

Between June 18 and July 9, 1979, Legionnaires' disease (LD) developed in 13 persons who had visited a hotel complex in Wisconsin. All had visited the part of the hotel that contains the restaurants and meeting rooms (building A). Legionnaires' disease occurred in 1% who had been exclusively in the meeting rooms and in 0.1% who had eaten only at the hotel restaurants. Furthermore, 1.5% exposed to meeting room 1 and none of those exposed only to the other meeting rooms had LD. Legionella pneumophila was isolated from water in the cooling tower on top of building A. Located within 5 m downwind of the cooling-tower exhaust, a chimney with an open damper allowed cooling-tower exhaust (as demonstrated by air tracer studies) to enter meeting room 1 via the fireplace. Although cases did not occur after the cooling-tower water was treated by continuous hyperchlorination and the chimney was sealed, a seven-day lag occurred between treatment and elimination of the organism from the tower water.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.