Abstract

This paper presents the results of spectrum analysis of leakage current waveforms on contaminated polymer insulators under fog conditions. This is a basic study on development of a monitoring for aging degree and surface pollution state using distortion rate(%) of 3rd and 5th harmonics according fundamental frequency[60Hz] under environment conditions. Arcing on the surface was always associated with distortion in the leakage current ; hence the low frequency components of the leakage current can be used as a means to evaluate the surface degradation. The results indicate that the distortion rate by spectrum analysis is available for the monitoring of contamination condition of EPDM Polymer insulators.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.