Abstract

This paper deals with the noise control of two power generator sets of 545 kW each, located in a Venezuelan resort. The generator sets made a noise level of 73 dB(A) at a distance of 47 m from the source, where are located the guest rooms. This level was far from the legal regulations for allowable environmental conditions. A noise enclosure with air silencers was proposed to reach a final level of 53 dB(A) at the guest accommodations. Two aspects must be taken into account, the noise reduction and the ventilation specifications of the generator sets, in order to keep the operational temperature. The final noise level was measured at 54 dB(A) and the pressure loss of the silencers was well placed into the ventilation specifications.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.