Abstract

Optimization design of heat exchangers based on entropy generation analysis is critical to improve the efficiency of CO2 refrigeration systems. However, most of the previous studies in this field were focused on individual components that are isolated from the entire system. Little has been done on the component analysis within the framework of entire refrigeration cycle. To probe this important issue, the entropy generation analysis is performed in this study on the fan-supplied gas cooler within a two-stage CO2 refrigeration system. The optimum circuit length is found by investigating the influences of geometrical parameters such as tube spacing, fin density and tube diameter on the heat transfer rate and entropy generation number of the gas cooler. The designed fan-coil is then put into the frame of the two-stage refrigeration cycle and its energy performance and exergy performance are both evaluated on the system level. The results show that the analysis with isolated gas cooler can lead to overestimated or unrealistic predictions on the heat transfer performance compared to the analysis within the framework of entire cycle.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.