Abstract

Abstract In order to achieve the optimization of the production process, power continuity is needed. The most important is the protection system, overcurrent relays are widely used as a primary relay to protect overload and short circuit. However, in some cases due to the nonlinearity pattern of the system, overcurrent relays does not grant the protection system. To overcome this problem, under-frequency and under-voltage relay are installed as a backup relay, but it also do not give the best result. This paper focused on the addition of reverse power relay to improve the system performance. Transient stability analysis is necessary to set reverse power relay because optimal power flow analysis cannot give proper parameter when a failure in grid happen. By arranging the delay time between those relays according to IEEE 242-2001, adequate coordination can be done. Moreover, the frequency and the voltage of the system stable at 100.04%, and 100.01%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.