Abstract

Building tight for minimizing building energy consumption and related carbon emissions might negatively affect indoor air quality (IAQ) if this is not correctly designed and evaluated during operation. To address this concern, a post occupancy evaluation study was conducted in a recent large office building in the Autonomous Province of Bolzano (Italy). The aim of the study was to collect evidence from a relevant case study and use it as a basis to define a standardized strategy for continuous monitoring of a larger portfolio of office buildings. Additionally, carbon dioxide (CO2), particulate matter (PM2.5, PM10), total volatile organic compounds (TVOC), air temperature, and relative humidity were recorded 24/7 for a 5-week period in winter 2023. Detailed spot measurements of VOCs and aldehydes were also carried out. Perceived air quality (PAQ) was evaluated through satisfaction surveys which covered various factors influencing PAQ including 14 potential sources of dissatisfaction. A cross-modal approach allowed for a comprehensive examination of the different domains (thermal, visual, acoustic, and IAQ) on PAQ. Measured contaminants’ levels were below recommended limits. Overall, participants were neither satisfied nor dissatisfied with PAQ, and possible related sources of dissatisfaction were elements such as the relative humidity. Sick building syndrome (SBS) selfreported symptoms such as dry skin and itchy eyes confirmed potentially too low relative humidity levels.