Abstract
The increase in power demand has forced the power system to operate closer to its stability limit. Voltage instability and line overloading have become challenging problems due to the strengthening of power system by various means. The nature of voltage stability can be analyzed by the production, transmission and consumption of reactive power. One of the major causes of voltage instability is the reactive power unbalancing which occurs in stressed condition of power system. Flexible AC transmission system (FACTS) devices play an important role in improving the performance of a power system, but these devices are very costly and hence need to be placed optimally in power system. FACTS device like thyristor controlled series compensator (TCSC) can be employed to reduce the flows in heavily loaded lines, resulting in a low system loss and improved stability of network. In this paper, a method based on line stability index, real power performance index and reduction of total system VAR power losses has been proposed to decide the optimal location of TCSC. The effectiveness of the proposed method is demonstrated on IEEE 30-bus power system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Power System Operation and Energy Management
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.