Abstract
The problem of electrohydrodynamic (EHD) condensation enhancement has been studied very recently. The electric field is commonly generated in such case by means of rod and mesh electrodes. The EHD method is suitable for dielectric media used in refrigeration and heat pump devices. The strong positive EHD effect has been obtained so far for vertical and horizontal bare tubes. However it was found that this effect for horizontal integral-fin tubes, commonly used in heat exchangers, is negligible small. The mechanism of the EHD condensation enhancement is discussed in the paper and a novel arrangement of the tube-electrode system is proposed. It consists of a horizontal finned tube with a rod type electrode placed beneath the tube. The experimental investigations have been carried out for this tube-electrode arrangement using HCFC-123 as a working medium. The obtained results confirmed the expectations since the application of EHD method for the new tube-electrode configuration increased the heat transfer coefficient from 27% to 110%, depending on the electrode potential. A simple model of the EHD condensate drainage has been proposed for the new tube-electrode arrangement.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.