Abstract

The number of wind turbines connected to the grid is steadily increasing in recent years. This situation forced the revision of the electric utilities grid codes requirements, to remain connected during grid faults, i.e., to ride through the faults, especially for those with power electronic converters, such as DFIGs. In fault condition, the voltage at the Point of Common Coupling (PCC) drops immediately and The grid voltage dips imposed at the connection point of the DFIG to the grid induce large voltages in the rotor windings, resulting in high rotor current, which can damage the rotor-side converter and disconnect from grid. In this paper, resistive and inductive superconducting fault current limiter (SFCL) is used to improve the fault ride- through (FRT) of wind turbine generation system (WTGS). The WTGS is considered as a variable-speed system, equipped with a DFIG. The analytical and simulation studies of the resistive SFCL for improving FRT capability are presented and compared with the inductive SFCL.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.