Abstract
Active damping methods are widely adopted to present a damping effect on the resonance phenomenon without the power loss of LCL-type converters connected to a grid. However, extra sensors are used to implement the damping strategy. In this paper, a sensorless damping strategy where only the grid current is sampled has been proposed. Furthermore, the inner relationship between the tradition capacitor current feedback strategy and the proposed strategy has been clarified. Considering the digital delay and a weak grid, a robust method that uses unit delay feedback to mitigate the phase lag and to widen the effective damping interval has been developed. With this simple measure, stability is enhanced during the Nyquist frequency and robustness is improved when the LCL parameters vary and grid impedance exists. Finally, simulation and experimental results are presented to verify the feasibility and engineering significance of the proposed strategy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.