Abstract
Upon the connection of wind generators to distribution grids, significant flicker emission can appear, due to the low $X/R$ ratios and low short-circuit levels at the points of connection. This paper proposes a reactive-power-based control scheme that aims for accurate cancellation of voltage flicker resulting from the grid connection of DFIG-based wind power. The control scheme operation is based on constructing the two-bus equivalent network of the detailed power system, via local measurements of voltage and active and reactive power flows at the DFIG terminals. The reactive power flow at the DFIG terminals is adjusted accordingly to cancel voltage flicker, based on the constructed equivalent network equations. The proposed control scheme avoids the use of power flow approximations at the connection point, and hence is free of the inaccuracies implicated in the conventional reactive-power-based flicker mitigation approaches (based on power factor control and voltage control). The proposed control scheme is shown, by comparative results, to provide superior performance to those conventional flicker mitigation approaches, as well as flicker mitigation capability independent of the connection point parameters.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.