Abstract
State feedback decoupling permits to achieve a better dynamic response for Voltage Source in stand-alone applications. The design of current and voltage regulators is performed in the discrete-time domain since it provides better accuracy and allows direct pole placement. As the attainable bandwidth of the current loop is mainly limited by computational and PWM delays, a lead compensator structure is proposed to overcome this limitation. The design of the voltage regulator is based on the Nyquist criterion, verifying to guarantee a high sensitivity peak. Discrete-time domain implementation issues of an anti-wind up scheme are discussed as well. Laboratory tests in compliance with the standard for UPS systems (IEC 62040-3) are performed to validate the theoretical analysis.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.