Abstract

Damping controller such as wide area PSS (WAPSS) employed on the excitation system is effective in interarea oscillation control. To well design a WAPSS, an accurate dynamic model should be established. With the development of wide area measurement system (WAMS) and low level probing tests, it is feasible to estimate a wide area dynamic model without large disturbance. However, as power capacity of the selected generator could be small, due to existence of ambient noise, the wide area probing response may be annihilated even the generator surfers from large disturbance. This paper presents an effective method to solve the aroused problem. Generators in the same station are combine-probed with the same signal for higher probing responses. Deviation analysis shows if parameters of the combine-probed generators are similar, the approach is feasible. A modified signal to noise ratio (SNR) is also provided to assess the probing responses. The whole work is carried out in a large complex system, China Southern Grid (CSG).

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.