Abstract

Today, many large commercial buildings use building automation systems to manage a wide range of equipment. This paper investigates the energy savings potential of several common heating, ventilation, and air conditioning (HVAC) system re-tuning measures on a typical large office building using the EnergyPlus software. Individual re-tuning measures simulated include automatic schedule adjustments, damper minimum flow adjustments, thermostat adjustments, as well as dynamic resets to static pressure, supply-air temperature, condenser chilled- and hot-water temperatures, and chilled and hot water differential pressure set points. All individual measures and combinations were simulated in 16 locations representative of different climates in the USA. Many of the demand-side individual measures were capable of reducing annual HVAC energy consumption by over 20% in most cities. Supply-side measures affecting HVAC plant conditions were only modestly successful (less than 5% annual HVAC energy savings). Some of the combinations revealed between 35% and 75% HVAC energy savings.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.