Abstract

Based on hour-by-hour simulation studies, this paper presents the annual energy consumption characteristics of water-panel type cooled-ceiling systems in comparison with conventional all-air systems. In particular, some unique energy saving measures associated with cooled-ceiling systems are numerically studied. The results indicate that a cooled-ceiling system can save much of the fan energy required in all-air systems, and that in the temperate Dutch climate, the system has a compatible energy performance with a VAV (variable air volume) system for office-building cooling purposes. The energy saving possibilities studied include using ceiling water to pre- or re-heat ventilation air and using a cooling tower for free cooling. The paper also demonstrates the possibilities of using a simulation technique to estimate non-conventional energy efficient system designs.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.