Abstract

According to a ward office building air conditioning system historical operation data, this article analyzed the number of air-conditioning cooling load operation, the time frequency and air conditioning systems circulating water temperature difference trend with air-conditioning load; proposed 4∶2∶4 group control method to the modular water chillers and air-conditioning water system energy-saving control scheme of variable frequency plus constant temperature difference. Energy-saving control system using Programmable Logic Controller (PLC) as the core controlling device was built, control logic was programmed. The running experiments show a remarkable energy-saving rate of 26.1%, with good energy efficiency and economy effects.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.