Abstract
Oversized equipment is one of the key factors for poor energy performance of commercial buildings in Hong Kong. Similar situations exist also in many buildings in different parts of the world. The use of realistic design criteria has been identified as an effective method to reduce the equipment oversizing problem. A set of realistic design criteria for lighting power density, occupation density, and appliances' load-intensity for various types of premises have been established based on data obtained in walk-through surveys of energy end-uses in 31 Hong Kong office buildings. Potential electricity savings through the use of realistic design criteria were estimated to be 6–22% of the electricity consumption of Hong Kong, which corresponds to an annual cost of HK$12.2–44.7 billion.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.