Abstract

This paper presents the field-measured energy performance of two common types of daylight-linked lighting control systems, continuous dimming and automatic on/off installed in two existing large atrium spaces located in Canada. The daylighting performance was evaluated based on the daylight contribution to the indoor illuminance and the amount of electrical lighting displaced by daylighting via the daylight-linked lighting control systems. Measured daylighting contribution to the space indicates that significant lighting energy savings can be achieved in atrium spaces if the daylight-linked lighting control system is appropriately selected, installed and commissioned throughout its existence. Results extrapolated from measurements collected during summer and winter indicate that as installed, the continuous dimming lighting control system provides 46% annual savings in electrical lighting consumption, while the automatic on/off saves between 11and 17% in lighting energy. These savings account for 68% of the lighting energy consumed during main occupancy for the continuous dimming system, and 31.5% for the automatic on/off. Operation irregularities such as a reduced dimming linearity and an incorrect adjustment of the phases of the dimming control system, as well as the inadequate location of the photocell controlling the automatic on/off lighting system, the improper maintenance of the skylight during winter and the oversizing of the lighting system reduced the energy efficiency of the lighting control systems by 30–65%.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call