Abstract

A hybrid PV-battery-diesel configuration is very attractive for stand-alone systems in terms of cost and reliability. In many applications, the battery and the diesel generator are centralized and generate the AC grid while the PV generators and loads are distributed and are connected to the grid. However, in these cases, long communication cables are required in order to reduce the PV power when the battery is fully charged. This paper proposes an energy management strategy which makes it possible to avoid the use of communication cables, rendering the system simpler, cheaper and more reliable. The strategy dictates that should a power reduction be required, the battery inverter increases the grid frequency. This is detected by the PV inverters, which continuously reduce their power in order to prevent the battery from overcharge or over-current. The strategy also optimizes the efficiency and operating life of the diesel generator. Simulation and experimental validation are carried out for a system with 10 kW PV generation, a 5 kVA battery inverter, a 5 kVA diesel generator and a 5 kVA load.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.