Abstract

The Takagi-Sugeno (T-S) fuzzy multiple-variable integral control system with fuzzy state observer is designed for the coordinated control of multi-input-multi-output (MIMO) nonlinear boiler-turbine system whose operating points vary within a wide range. Linear models are first derived from the original nonlinear model on several operating points. Next the fuzzy multi-variable integral controller and the fuzzy state observer are designed via using the parallel distributed compensation (PDC) scheme, and the T-S fuzzy control system is constructed with the drum pressure as the premise variable. The problem that part of state variables can not be measured is successfully solved by introducing fuzzy state observer. Last the stability analysis is given by means of linear matrix inequality (LMI) approach, and the control system is guaranteed to be stable within a large range. The simulation results demonstrate that the control system works well over a wide region of operation.