Abstract

Present work compares the performance of commercially available 170 kW vapor compression chiller with equivalent three configurations (parallel, series and combined series-parallel) of VCAIRS (vapor compression-absorption integrated refrigeration system) based on combined energy, exergy, economic and environmental (4E) analyses. Parallel, series and combined series-parallel configurations reduces the energy (electricity) consumption in the compressor by 50%, 76.8% and 88.3% respectively and consequently, reduce the significant amount of CO2 emission. Comparative exegetic analysis based on modified Gouy–Stodola law was performed which predicted higher irreversibility rate as compared to conventional approach. The thermoeconomic study shows that annual cost of the plant operation is 13.8%, 20.9% and 24.7% less for parallel, series and combined series-parallel configurations respectively as compared to equivalent VCRS (vapor compression refrigeration system) and after optimization, the same is further reduced by 8.1%, 8.5% and 4.7% respectively from the base value.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.