Abstract
This work aims at achieving enhanced energy conservation for space conditioning with the application of a new combined variable air volume (VAV)-based chilled water air conditioning (A/C) system and thermal energy storage (TES) system. The phase change material (PCM) used in this system exhibited good charging and discharging characteristics that directly helped in conserving the overall energy spent on cooling and ventilation. The present system was experimentally investigated for summer and winter climatic conditions under demand controlled ventilation (DCV) and DCV combined with the economizer cycle ventilation (ECV) to substantiate its energy savings capability. Based on the results, in the DCV and combined DCV–ECV modes, this system achieved 28% and 47% of per day average energy conservative potential, respectively, while compared to the conventional chilled water-based A/C system. Similarly, the VAV–TES system yielded an on-peak total energy savings of 38% and 42%, respectively, for the same operating conditions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.