Abstract

The paper investigates whether air-water heat exchanger with longitudinal fins along the air flow direction are an appropriate means to reduce pressure loss in mechanical ventilation systems, compared to conventional heating coils.To answer this question, theoretical calculations regarding pressure loss and heat transfer are performed and the results are checked by measurements. It is found that a longitudinal fin heat exchanger with 30 radially arranged fins and an overall length of 830mm transfers the same heat flow as a conventional heating coil (∅ 125). The pressure loss only adds up to about 60% to 70%, so a reduction of 30% to 40% can be achieved. Additionally it is expected, that the longitudinal fin heat exchanger is more suitable for efficient low temperature heating systems, because of the counter-current heat transfer. The disadvantage of its increased length can be compensated by integrating the longitudinal fin heat exchanger in a duct silencer, which is required anyway. Hence, the energy efficiency of mechanical ventilation system can be increased.