The main thrust of this paper is directed toward a novel air conditioning system that can maintain a healthy indoor environment and be energy-efficient. This system consists of a low-temperature regenerative periodic total heat exchanger, radiant ceiling-cooling coil, and conventional air conditioner. The natural cold energy of the tap water in the cooling coil provides comfortable and uniform cooling, and the desiccant-packed bed in the total heat exchanger recovers the indoor energy to handle the fresh air. The performance of each component is discussed, and the actual performance of the whole system is investigated in an office at the Taipei Water Department. The results indicate that using a radiant ceiling-cooling coil to precool the indoor environment enables the traditional window-type air conditioner to reduce two-thirds of the original operating time. In addition, the test of the whole system was conducted in the same office, and it was observed that using this system to handle the incoming air could save 13%–19% of the energy consumption per month during a year-round operation compared to directly introducing untreated fresh air.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.