Abstract
In this study, various energy conservation measures (ECMs) on heating, ventilating and air conditioning (HVAC) and lighting systems for a four-storied institutional building in sub-tropical (hot and humid climate) Queensland, Australia are evaluated using the simulation software called DesignBuilder (DB). Base case scenario of energy consumption profiles of existing systems are analysed and simulated first then, the simulated results are verified by on-site measured data. Three categories of ECMs, namely major investment ECMs (variable air volume (VAV) systems against constant air volume (CAV); and low coefficient of performance (COP) chillers against high COP chillers); minor investment ECMs (photo electric dimming control system against general lighting, and double glazed low emittance windows against single-glazed windows) and zero investment ECMs (reset heating and cooling set point temperatures) are evaluated. It is found that the building considered in this study can save up to 41.87% energy without compromising occupancies thermal comfort by implementing the above mentioned ECMs into the existing system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.