Abstract
This paper reports on the energy implications of HVAC system configuration by analyzing the energy balance and psychrometrics of typical and innovative systems. Three criteria were shown to be significant: (1) the ability to minimize outside air load, (2) the ability to eliminate simultaneous cooling and heating and use mixing effectively, and (3) the availability of interzonal airflow. Configurations that meet these criteria would be able to deliver the desired indoor air quality with reduced energy consumption. The performance of ten two-zone system configurations, including single-duct, dual-duct, fan-coil-based variations, and other specialized systems in the literature, were analyzed for a number of operational conditions. The results confirmed that fan-coil-based configurations with interzonal airflow paths perform better than other configurations. The conclusion of this study may be used as a guideline for multi-zone system designs.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.