Abstract

The paper describes a parametric study developed to estimate the energy and peak power savings potential of radiant cooling systems in commercial buildings in the US. The study is based on the numerical modeling of a radiant cooling system and an all-air system at different locations in the US. The results show that a building equipped with a radiant cooling system can be operated in any US climate with low risk of condensation. For the office space examined in the study, employing a radiant cooling system instead of a traditional all-air system can save on average 30% of the energy consumption and 27% of the peak power demand due to space conditioning. The savings potential is climate-dependent, and is larger in retrofitted buildings than in new construction.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.