Abstract

Energy analysis is important to analyze energy consumption pattern, monitoring on how the energy used varies with time in the building and how the system element interrelate. In this case study, a preliminary energy audit is done on lighting and air-conditioning system. The lighting and airconditioning system consume the highest amount from the total building energy usage. The study was conducted in the Faculty of Mechanical Engineering Building, Universiti Teknikal Malaysia (UTeM) Technology Campus. From the result shows that the air-conditioning system has contributed approximately 48.8% from the total monthly energy usage. The estimation of Building Energy Index (BEI) for the cooling load is 655.19 kWh/m²/year. Meanwhile, the BEI for lighting system is found approximately 150 kWh/m2/year.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.