Abstract

a substation yard with return plane to emulate the ground grid and other ground conductors near the yard cable, cabinetry housing the installed DPRs, station battery and battery charger, terminal block elements, and a breaker simulator to emulate a substation yard configuration. The DPRs were powered from the station battery and the transformer inputs energized with a three-phase source to maintain typical operating conditions during the tests. Vulnerability testing consisted of a conducted E1 pulse injected into the center of the yard cable of the DPR circuits. Current measurements on the yard cable and DPR inputs indicated significant attenuation of the conducted pulse arriving at the control house equipment from the emulated substation yard. This reduction was quantified with respect to the equivalent open-circuit voltage on the yard cable. No equipment damage or undesired operation occurred on the tested circuits for values below 180 kV, which is significantly higher than the anticipated coupling to a substation yard cable.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.