Abstract

This paper presents a novel hybrid converter configuration for conventional Line-Commutated Converter (LCC) HVDC technology aiming to eliminate commutation failures under serious faults. Dynamic series insertion of capacitors during commutation is utilized to increase the effective commutation voltage. The operating principles are presented followed by detailed mathematical analysis for both zero impedance single-phase and three-phase faults in order to select the required capacitor size and its voltage level. The performance of the proposed method is validated by simulation results in Real Time Digital Simulator (RTDS) and the results show that the proposed converter configuration is able to eliminate commutation failures under both fault cases. Consequently partial power transferring capability during single-phase fault and fast fault recovery from three-phase fault can be achieved. Further simulation results show that the harmonic content of inverter AC voltage and current are not significantly increased and the voltage stress of the thyristor valve is comparable to that of the original benchmark system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.