Abstract

For low-power grid-connected applications, a single-phase converter can be used. In photovoltaic (PV) applications, it is possible to remove the transformer in the inverter to reduce losses, costs, and size. Galvanic connection of the grid and the dc sources in transformerless systems can introduce additional ground currents due to the ground parasitic capacitance. These currents increase conducted and radiated electromagnetic emissions, harmonics injected in the utility grid, and losses. Amplitude and spectrum of the ground current depend on the converter topology, the switching strategy, and the resonant circuit formed by the ground capacitance, the converter, the ac filter, and the grid. In this paper, the ground current in a 1.5-kW PV installation is measured under different conditions and used to build a simulation model. The installation includes a string of 16 PV panel, a full-bridge inverter, and an LCL filter. This model allows the study of the influence of the harmonics injected by the inverter on the ground current.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.