Abstract

The paper analyses some ignition incidents that have been reported with insulating, (non-conductive) underground plastic pipes in retail petrol stations. The occurrence of the incidents is compared with voltage measurements, observations of the typical spread of streaming currents recorded in gasoline handling and theoretical estimates of the voltages on the pipes. The comparisons suggest that neither incendive sparks from unbonded conductors nor incendive brush discharges from insulating pipe surfaces can be ruled out although both are expected to be rare. The hazards can be prevented by using pipes with earthed conductive or dissipative inner linings.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.