Abstract

Electromagnetic time reversal (EMTR) has recently been applied to the problem of fault location in AC and DC power grids. In this paper, we present an analysis of the effect of losses on the application of EMTR to locate faults. Three models for the back propagation are proposed and discussed. We show that a back-propagation model in which the losses are included results in a perfect estimation of the fault location, even though in this case the telegrapher's equations are not strictly time-reversal invariant.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.