Abstract

IEC TR61400-24 [1] suggests interconnection of the grounding system of wind turbines to achieve low steady-state resistance, however, the transient behavior during a lightning strike to the interconnected wind turbine grounding system remains to be discussed. This paper investigates the influence of interconnection on the lightning surge response of wind turbine grounding system. Two different numerical methods, Numerical Electromagnetics Code (NEC-4) based on Method of Moments (MoM), and Virtual Surge Test Lab (VSTL) based on Finite Difference Time Domain (FDTD) method are used for electromagnetic analysis of lightning surge response of wind turbine grounding system. Comparison of results using NEC-4 and VSTL are made to clarify the usefulness of these methods for transient analysis of a large grounding system. The influences of resistivity of soil and front time of lightning impulse current, on the response of interconnected wind turbine grounding system are analyzed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.