Abstract

In a previous paper (1), the necessary experimental and theoretical basis was established for a discussion of the effect of electrode area on the 60-cycle breakdown of transformer oil. A study of 1600 observations established the extremal nature (2) of such breakdown distributions and yielded an equation relating area and voltage which agreed closely with test results. This equation is: V A1 − V A2 = s v /σ N 1n A 1 /A 2 (1) where V is the modal strength and s v is the standard deviation of N measured breakdown values; σ N is a function of the number of breakdowns N only.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.