Abstract

Composite insulators have been widely used in high voltage transmission lines more than 20 years in China due to their hydrophobic properties, relatively low weight and maintenance costs, and high mechanical strength. Shed configuration is a key factor that influences flashover voltage of composite insulators under icing conditions. In order to study the effect of shed configuration on the flashover performance of composite insulators under icing conditions, the electrical performance of five types of 330-kV composite insulators with different shed designs were compared under artificial icing conditions. Experiments were carried out in the multi-function climate chamber in Chongqing University. In order to explain the influence of shed configuration, electric field and potential distributions along each insulator type were calculated numerically using the finite element method (FEM). The numerical simulation results were found to be in agreement with the laboratory experimental ones.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.