Abstract

Electrical design and withstand test of mini-model coils for high temperature superconducting fault current limiter (HTSFCL) have been studied. Electrical insulating factors of the HTS coil for HTSFCL are turn-to-turn and layer-to-layer. The electrical insulation of turn-to-turn depends on surface length, and the electrical insulation of layer-to-layer depends on surface length and breakdown strength of LN/sub 2/. Therefore, two basic characteristics of breakdown and flashover voltage were experimentally investigated to design electrical insulation for 6.6 kV Class HTSFCL. We used Weibull distribution to get electric field strength for insulation design. And mini-model coils for HTSFCL were designed by using Weibull distribution and were manufactured to investigate breakdown characteristics. The mini-model coils were passed in impulse withstand test as well as AC withstand test.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.