Abstract
This work presents an extension of our previous work on voltage stress analysis of a 3MVA, 33/11kV, 3-phase, 50Hz, Dyn 11 transformer against the application of standard and non-standard impulse voltages. A preliminary comparative study on the variation of maximum voltage to ground and voltage across the coils under different impulse voltages indicated that non-standard impulse voltage waveforms develop higher voltage stress in the windings. They pose high risk and are critical to transformer insulation system. The obtained test results provide the basis for further study of non-standard impulse voltage waveforms and make necessary correction in the existing impulse testing standards. However, to take care of the stringent effect of actual lightning and other impulse voltages occurring in practical field a more detailed study considering a wide variety of non-standard impulse voltage waveforms is aimed to be done in future.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.