Abstract
The increasing use of single phase rectifiers for electric power conversion in residential applications increases harmonic load on utility systems. Many papers have analyzed the effect of these loads on power quality and equipment loadability. However, there are two more critical concerns for harmonic loads served phase to neutral on multi-grounded wye systems. Triplen harmonics, particularly the third, add in the neutral and have little diversity between loads. The higher neutral currents may cause significant problems. Neutral to earth voltages will increase near the substations which could increase stray voltage complaints. The additional neutral current on three phase lines will elevate EMF levels especially in the fringe areas. This paper provides fundamental understanding of triplen harmonic influence on stray voltage and EMF related to multi-grounded wye electric distribution systems.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.