Abstract

Problem statement: Under-Voltage Load Shedding (UVLS) protection of Electric Power Systems (EPS) is frequently used against Voltage Collapse (VC), however when there is automatic bus voltage regulation with excessive capacitive compensation, the UVLS scheme may not trip. In this case, load shedding must be based in a Voltage Collapse Proximity Indicator (VCPI). Many UVLS procedures may not be appropriate today. Approach: In order to elucidate the problem stated, several studies were carried out using MatLab/SimPowerSystems. In the first case, it was simulated a reduced electric system consisting of an infinite-bus feeding a load through a large impedance line. Two other cases were simulated now including a fixed capacitive impedance (representing a saturated SVC or similar) with 25 and 60 MVAr, both with a generator regulating the load bus voltage. Graphic curves representing the load bus voltage versus time were obtained with the application of a ramp power load. Results: In all cases the curves showed if there was sufficient time to command the UVLS scheme. The usual UVLS criteria failed for the third case. As the capacitive reactive power of the saturated compensation devices was increased, their equivalent capacitance, corresponding to the sum of maximum MVAr capacities, grows. The load demand increase, after MVAr saturation, can cause a voltage decrement which is too fast for UVLS adequate operation. Conclusion/Recommendations: Based in past experiences, any operator could be confident on existing UVLS protection of some area, but a VC can occur with the current situation without UVLS trip, as stated. It was suggested to check the current UVLS operation conditions, especially in areas where there was a growth of both load demand and reactive power resources. When UVLS method is found ineffective, then a suggestion is to replace it by a technique based upon some VCPI.

Highlights

  • There are many Under-Voltage Load Shedding (UVLS) schemes in operation around the world, because they provide a low cost protection technique against voltage collapse

  • As the load demand is increased new specific devices are installed to supply the required reactive power in order to keep the bus voltage level within standard limits. This reactive power can be provided by shunt capacitors bank, Static VAr Compensator (SVC), Static Compensator (STATCOM) and other Flexible AC Transmission Systems (FACTS) devices

  • The Voltage Collapse (VC) phenomenon occurs with saturated reactive power sources represented by a 25 MVAr capacitor bank and the generator voltage regulation in operation till it reaches the over voltage limit

Read more

Summary

Introduction

There are many UVLS schemes in operation around the world, because they provide a low cost protection technique against voltage collapse. The operation of installed UVLS can no longer give EPS protection against VC, after continuously growth of installed load demand followed by reactive power injection at system buses. As the load demand is increased new specific devices are installed to supply the required reactive power in order to keep the bus voltage level within standard limits. This reactive power can be provided by shunt capacitors bank, Static VAr Compensator (SVC), Static Compensator (STATCOM) and other Flexible AC Transmission Systems (FACTS) devices

Methods
Discussion
Conclusion
Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call