Abstract

Satisfactory operation of composite insulators is intimately related to the surface electric field (stress) distribution. This paper presents results of calculation of the electric field distribution for composite insulators up to 1200 kV, using a 3D software package based on the Boundary Element Method. The impact of corona and grading rings, single and bundled conductors, insulator orientation (dead-end and suspension), single and double units, and surface condition (dry and wet) on the electric field distribution has been analyzed. For UHV systems (higher than 750 kV ac) the use of dual insulators with individual corona rings at the line and ground end and a common grading ring at the line end is beneficial. The existence of optimal dimensions of corona and grading arrangement has been illustrated on a 1000 kV insulator string. It was found that the dead end insulators experience higher electric stress when compared to their suspension counterparts and this difference gets more prominent as the system voltage increases.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call