Abstract

Extremely low frequency (60 Hz) electric and magnetic field levels were measured at three Canadian pulp and paper mills, using area point-in-time measurements. Most electric field levels were below the limit of detection of 1 V/m (92 of 132 measurements); the highest measured field was 47 V/m. Measured magnetic field strengths ranged from less than the limit of detection (0.125 mG, 2 of 132 measurements) to 706 mG, with a median of 1.6 mG. Magnetic field levels were higher in mills that consume more electric power, but worker exposures could not be predicted according to plant power consumption. Overall, electric and magnetic field levels in the three pulp and paper mills were similar to those experienced by the general population. However, maximum magnetic field intensities in some areas were as high as those experienced by electrical workers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.