In this paper, the proposed hierarchical control scheme adds new control loop to control the reactive power reference by a fuzzy logic controller to have the benefit of increasing the system stability margins and moreover, eigenvalue, robustness and time delay analysis of proposed control scheme are presented. The reported droop-based control methods of VSI-based microgrids including hierarchical droop-based control scheme are limited to primary and secondary control levels while the proposed control scheme is completely analyzed so that the three hierarchical control levels modeled for both grid-connected mode and islanded mode. This scheme maintains the stability of microgrids not only for the small-signal events, but also for large-signal disturbances such as three phase and single phase to ground faults, heavy motor starting, etc. However, power sharing to loads and network is sufficiently done. To demonstrate the effectiveness of the proposed hierarchical controller, simulation studies have been performed on a microgrid consisting of four units of distributed generation with local loads and in presence of main grid using MATLAB/SIMULINK software and validated using OPAL RT real-time digital simulator.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.