Abstract
Efficient Removal Performance of COD in Real Laundry Wastewater via Conventional and Photo-Fenton Degradation Systems: A Comparative Study on Oxidants and Operating Time by H2O2/Fe2+
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.