Abstract

In recent years, energy conservation has become a major focus in the industrial sector. Many office buildings in Japan achieve energy savings by introducing highly efficient equipment and systems, such as high-temperature cooling water (14 °C), which increases heat source efficiency. However, such equipment requires adjustments to increase operational efficiency. In this case study, the efficiency of equipment using high-temperature cooling water was further improved through operation control optimization. The energy efficiency before and after the improvement was compared. The target building has chilled and hot water supplied to each floor from district heating and high-temperature chilled water supplied from cooling chillers on the rooftop. The energy consumption of two floors was evaluated: a subjective floor with equipment using high-temperature cooling water installed, and a common floor with a conventional system. After on-site verification, changes were made to the operation control of the cooling towers, condenser pumps, primary pumps, secondary pumps, and air handling units. As a result, the coefficient of performance of the water-cooled chiller and the whole system improved by 0.40 and 0.45, respectively. The flow rate of the air conditioning equipment using high-temperature cooling water decreased while maintaining an equivalent amount of heat extraction. In conclusion, the efficiency of the equipment was further improved by operation control optimization.

Highlights

  • In recent years, energy conservation has become a major focus in various fields, including building engineering

  • In order to compare the effect of the operation control, the coefficient of performance (COP) of the watercooled chillers and the entire system was calculated

  • The water-cooled chiller COP was calculated by dividing the amount of heat extraction from the chiller by the primary energy consumption of the chiller [4]

Read more

Summary

Introduction

Energy conservation has become a major focus in various fields, including building engineering. Many tenant office buildings in Japan achieve energy savings by introducing highly efficient equipment, such as air conditioning using high-temperature chilled water (14 °C). It is necessary to review and improve the operation control of such equipment after installation in order for it to operate efficiently. Energy consumption is evaluated by analyzing data from the building energy management system (BEMS) to identify further possibilities for improving energy savings. The aim of this study was to evaluate the efficiency of equipment using high-temperature cooling water in an office building before and after improvements in operation control

Objectives
Methods
Results
Conclusion
Full Text
Published version (Free)