Alleviation of voltage limit violation at certain critical buses is a serious problem in the interconnected power system. In this paper, an attempt is made, based on the concept of local optimisation, to alleviate the voltage limit violation by using controls at the local level during any severe disturbance to avoid system collapse. The method is efficient and robust in comparison with existing methods, as the new secure operating point is obtained with minimum control action. The algorithm developed in this paper gives satisfactory results when tested under steady-state conditions on 24 bus IEEE (RTS) and 57 bus IEEE systems under severe and extreme loading conditions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEE Proceedings - Generation, Transmission and Distribution
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.