Abstract
Filtration efficiency of high-efficiency particulate air (HEPA) filters is said to be over 99.97% of removal rate against the mist of thermogenerating-type of dioctyl phthalate with average particles diameter of 0.3 micrometer, as tested by the U.S. Military Standard 282 (1956). Filtration of bacterial aerosols through commercial air filters was tested to examine the efficiency of bacterial filtration with eight kinds of air filters. Percentage of bacterial filtration efficiency (% BFE) of three kinds of HEPA filters showed 100% BFE, while NBS-95 and NBS-85 showed over 99% BFE. BFE of NBS-75 air filter was 91.75%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: THE BULLETIN OF TOKYO MEDICAL AND DENTAL UNIVERSITY
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.